(includes backbox, power supply, technical manual, and a frame & post operating instruction sheet) for single and dual. N-ANN-80(-W): LCD Annunciator is a remote LCD annunciator that mimics the information displayed on the FACP LCD. User supplied graphic annunciator. (See DN-7105). ANN-SEC: Optional card for a secondary ANN-BUS. N-ANN-80: LCD Annunciator is a remote LCD annunciator that. Serial/Parallel Printer Gateway module provides a connection for a serial or parallel printer. N-ANN-I/O: LED Driver Module provides connections to a user-supplied graphic annunciator. DP-51050: Dress panel (red) is available as an option.

  1. Lcd 80 Annunciator
  2. Firelite Annunciator Ann 80
  3. Ann 80 Annunciator Manual
  4. Ann 80 Annunciator

N-ann-80, Character lcd serial annunciator, General

Advertising

dn-7114:c • 5/22/09 — Page 1 of 2

N-ANN-80

80-Character LCD
Serial Annunciator

Annunciators

dn-7114:c • A1-65

71

14c

ov

.jpg

General

The N-ANN-80 annunciator is a compact, backlit, 80-character

LCD fire annunciator that mimics the Fire Alarm Control Panel

(FACP) display. It provides system status indicators for AC

Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi-

tions. The N-ANN-80 and the FACP communicate over a two-

wire serial interface employing the ANN-BUS communication

format. Connected devices are powered, via two additional

wires, by either the host FACP or a remote UL-listed, filtered

Ann

power supply. N-ANN-80 is black; for white order N-ANN-80-W.
The N-ANN-80 displays English-language text of system point

information including device type, zone, independent point

alarm, trouble or supervisory status, as well as any custom

alpha labels programmed into the control panel. It includes con-

trol switches for remote control of critical system functions. (A

keyswitch prevents unauthorized operation of the control

switches.)
Up to eight N-ANN-80s may be connected to the ANN-BUS of

each FACP. Minimal programming is required, which saves time

during system commissioning. The N-ANN-80 is compatible

with NOTIFIER FACPs with an ANN-BUS, such as the NFW-50.

Features

• Listed to UL Standard 864, 9th Edition.
• Backlit 80-character LCD display (20 characters x 4 lines).
• Mimics all display information from the host panel.
• Control switches for System Acknowledge, Signal Silence,

Drill, and Reset.

• Control switches can be independently enabled or disabled

at the FACP.

• Keyswitch enables/disables control switches and mechani-

cally locks annunciator enclosure

• Keyswitch can be enabled or disabled at the FACP.
• Enclosure supervised for tamper.
• System status LEDs for AC Power, Alarm, Trouble, Supervi-

sory, and Alarm Silence.

• Local sounder can be enabled or disabled at the FACP.
• N-ANN-80 connects to the ANN-BUS terminal on the FACP

and requires minimal panel programming.

• Displays device type identifiers, individual point alarm, trou-

ble, supervisory, zone, and custom alpha labels.

• Time-and date display field.
• Surface mount directly to wall or to single, double, or 4'

square electrical box.

• Semi-flush mount to single, double, or 4' square electrical

box. Use ANN-SB80KIT for angled view mounting.

• Can be remotely located up to 6,000 feet (1,800 m) from the

panel.

• Backlight turns off during AC loss to conserve battery power

but will turn back on if an alarm condition occurs.

• May be powered by 24 VDC from the host FACP or by remote

power supply (requires 24 VDC).

• Up to eight N-ANN-80s can be connected on the ANN-BUS.

Lcd 80 Annunciator

Controls and Indicators

• AC Power
• Alarm

• Trouble
• Supervisory
• Alarm Silenced

Specifications

Operating voltage range: 18 VDC to 28 VDC.

N-ann-80 Serial Annunciator User Manual

Current consumption @ 24 VDC nominal (filtered and non-

resettable): 40 mA maximum.

Ambient temperature: 32°F to 120°F (0°C to 49°C).

Relative humidity: 93% ± 2% RH (noncondensing) at 32°C

± 2°C (90°F ± 3°F).

• 5.375” (13.65 cm.) high x 6.875” (17.46 cm.) wide x 1.375”

(3.49 cm.) deep.

• For use indoors in a dry location.
• All connections are power-limited and supervised.

Agency Listings and Approvals

The listings and approvals below apply to the N-ANN-80. In

some cases, certain modules may not be listed by certain

approval agencies, or listing may be in process. Consult factory

for latest listing status.

UL: S635

• FM approved

CSFM: 7120-0028:240

MEA: 442-06-E Vol. 2

The ANN-BUS

Annunciator

POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY

The ANN-BUS can be powered by an auxiliary power supply

when the maximum number of ANN-BUS devices exceeds the

ANN-BUS power requirements. See the FACP manual for more

information.

Advertising
Popular Brands
Popular manuals
Advertising

38

50 Pt Addr Panel

PS-Tools

08/2010

Configuring Fire Panels

ANN-80 Options

The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics
the display on the control panel annunciates device type, point alarm, trouble or supervisory
condition, zone assignment plus any custom alpha labels programmed into the FACP.
Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial
interface employing the ANN-Bus communication format.

To configure the ANN-80 module

1.

Select Yes to enable the Lock Enable option which allows you to unlock the ANN-80 keypad
with its own key. If you select No, the keylock is ignored and the ANN-80 keypad buttons are
always enabled.

2.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80 module. The piezo sounder is disabled when you select No.

3.

Select Yes in ACK Enable to enable the normal function of the ACK Button on any installed
ANN-80 annunciator. This option is ignored if you select No.

4.

Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80
annunciator.

5.

Select Yes in Reset Enable to enable the Reset Button on any installed ANN-80 annunciator.

6.

Select Yes in DrillEnable to enable the Drill Button on any installed ANN-80 annunciator(see

).

Note

You must enable the canadian option to configure the following ANN-80C modules.

To configure the ANN-80C module

1.

Select Yes in Piezo Enable to enable the sounding of the piezo sounder on any installed
ANN-80C module. The piezo sounder is disabled when you select No.

2.

Select Yes in Step Enable to enable the normal function of the Step Button on any installed
ANN-80C annunciator. This option is ignored if you select No.

3.

Select Yes in Silence Enable to enable the Silence Button on any installed ANN-80C
annunciator.

4.

Select Yes in LampTest Enable to enable the lamptest Button on any installed ANN-80C
annunciator.

5.

Firelite Annunciator Ann 80

Select Yes in Sounder TestEnable to enable the sounder Button on any installed ANN-80C
annunciator.