Rockwell Automation Publication 520-QS001A-EN-E - March 2014

11

Allen-Bradley PowerFlex 523 Manuals & User Guides. User Manuals, Guides and Specifications for your Allen-Bradley PowerFlex 523 Controller. Database contains 2 Allen-Bradley PowerFlex 523 Manuals (available for free online viewing or downloading in PDF): Original instructions manual, Quick start manual. Troubleshooting your Allen Bradley PowerFlex 40 AC drive begins with a fault condition that occurs while operating or starting up. The status of your drive is monitored at all times and any changes in the status will be indicated through the keypad. A fault is a condition that stops the drive and there are two types of.

PowerFlex 520-Series Adjustable Frequency AC Drive

Control Terminal Block

PowerFlex 523 Control I/O Wiring Block Diagram

04

05

06

01

02

03

11

12

13

14

15

C1

C2

Digital Common

DigIn TermBlk 05/Pulse

DigIn TermBlk 06

Stop

(1)

DigIn TermBlk 02/

Start/Run FWD

(2)

DigIn TermBlk 03/

Direction/Run REV

R1

R2

Relay N.O.

Relay Common

+24V DC

+10V DC

0-10V Input

Analog Common

4-20mA Input

RJ45 Shield

Comm Common

+24V

+10V

Typical

SNK wiring

Typical

SRC wiring

R1

11

12

13

14

User

15

C1

C2

R2

R3

01

02

03

04

05

06

Pot must be

1...10 k ohm

2 W min.

SNK

D

igital In

D

igIn T

ermBlk

05

Se

l

J7

J8

Pulse In

SRC

Digital

Input

SRC

SNK

R3

Relay N.C.

81

RS485

(DSI)

(1)

(2) Two wire control shown. For three wire control use a momentary input

on I/O Terminal 02 to command a start. Use a maintained input

for I/O Terminal 03 to change direction.

(3) Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.

IMPORTANT

Allen Bradley Powerflex 523 Parameters

I/O Terminal 01 is always a stop input. The stopping mode is determined by the drive setting.

The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this jumper when using I/O
Terminal 01 as a stop or enable input.